س
أرسل استفسارك اليوم
اقتباس سريع

Mastering Reheating Furnace Operation and Shutdown for Wire Rod and Bar Mills

Reheating furnaces play a critical role in the production of wire rod and bar steel, ensuring proper temperature control before rolling. Proper operation and shutdown procedures are essential to maintain steel quality, كفاءة الطاقة, و operator safety. This guide provides a comprehensive, step-by-step overview of reheating furnace operation, heating system management, و safe shutdown practices—key knowledge for mill operators, furnace technicians, و steel plant engineers.

Part 1: Heating Operation Procedures

1. Know Your Steel Grade

Before starting operations, the furnace operator must confirm the درجة الصلب و material specification inside the furnace. Temperature settings must be adjusted accordingly to meet metallurgical requirements.

2. Three-Zone Temperature Control

Strictly follow the three-zone heating protocol:
  • Soaking zone: 1000-1200 درجة مئوية
  • Heating zone: 900-1200 درجة مئوية
  • Preheating zone: >650درجة مئوية
This ensures uniform heating and prevents thermal stress or defects.

3. Valve and Control Settings During Heating

  • Use timed reversal mode for the reversing system.
  • Keep the gas quick-shutoff valve OPEN.
  • Ensure the purge valve is CLOSED.

4. Furnace Pressure Management

Maintain furnace pressure between 0–20 Pa, ideally at a slight positive pressure. Use electric continuous regulation for precise control.

5. Air-Gas Ratio and Flow Control

Temperature is regulated by adjusting air and gas flow rates and their ratio:
  • Standard air-to-gas ratio: 0.8:1
  • Max gas flow:
    • Preheating & heating zones: ≤22,000 m³/h
    • Soaking zone: ≤4,600 m³/h
Optimize combustion for complete burning and target temperatures.

6. Adjust for Rolling Conditions

  • Monitor furnace and rolling status closely.
  • If rolling stops or delays occur, discharge billets periodically to avoid sticking (billets welding together).
  • If sticking is suspected:
    • Do NOT lower soaking zone temperature
    • Increase discharge speed
    • Gradually reduce temperature afterward

7. Temperature Control Based on Delay Time

表格
Delay Duration Target Soaking Zone Temp
≤20 min No reduction
20–40 min 1050درجة مئوية
40–60 min 950درجة مئوية
60–300 min 850درجة مئوية
>300 دقيقة Shut down furnace

8. Monitor Vaporization Cooling System

  • Watch boiler drum water level; respond immediately to alarms.
  • Cooling water outlet temperature at furnace tail must be ≤50°C. Increase water flow if exceeded.

9. CO Safety in Gas Hazard Zones

  • Safe CO concentration: <400 ppm
  • If exceeded:
    • Evacuate immediately
    • Mark area as hazardous
    • Assign personnel to monitor
    • Report to central control

10. Respond to Alarm Systems

  • Over-temperature alarm:
    • Furnace temp high → Adjust air/gas flow
    • Flue gas temp high → Force reversal
  • Valve position alarm: Notify instrumentation team
  • If unresolved or system auto-shuts down:
    • Close main gas electric valve
    • Keep blower and reversal system powered
    • Log all actions

Part 2: Heating System Operation Guidelines

1. Dynamic Air-Gas Adjustment

Continuously adjust air and gas supply based on production load و temperature feedback.

2. Flue Gas Temperature Limit

Normal flue gas temperature must remain below 170°C.

3. Furnace Pressure Fine-Tuning

If pressure exceeds 20 Pa:
  • Open the damper on the side with lower flue temperature
  • Close it if pressure is too low

4. Emergency Response to Alarms

On “valve” or “over-temp” alarms:
  • Minimize blower damper
  • Close main gas valve
  • Diagnose fault via indicator lights
  • Never stop the blower during troubleshooting

5–6. Diagnosing Specific Alarms

  • Valve alarm: Check actuator, solenoid, or sensor; involve controls team
  • Over-temp alarm: Identify which flue exceeds 170°C; inspect dampers, cylinders, and control valves

7. Automatic Safety Shutdown

On system failure:
  • Both induced draft fans and gas shutoff valve close automatically
  • Purge valve opens → furnace enters automatic purge mode
  • Reduce air damper manually; blower remains ON

8. System Recovery After Fault

After fixing the issue:
  1. Power-cycle the control system
  2. Press “Purge Valve Close” button
    • Gas quick valve reopens
    • Purge valve closes
    • Fans restart
  3. If furnace temp <800درجة مئوية:
    • Switch reversal to temperature-controlled mode
    • Relight pilot burners

9. Standard Operating State

During normal heating:
  • Reversal mode: Timed control
  • Gas quick valve: يفتح
  • Purge valve: Closed

10. PLC Failure Protocol

If PLC crashes or freezes:
  • Cut power to reversal control system
  • Close main gas electric valve
  • Manually shut air dampers for soaking & heating zones

Part 3: Safe Furnace Shutdown Procedure

1. Initiate Shutdown on Command

Begin only after official shutdown notice.

2. Isolate Fuel Supply

  • Close all air and gas dampers to minimum
  • Shut the main gas blind valve

3. Activate Purge Sequence

  • Turn off reversal control → system auto-enters purge mode
  • Induced fans, gas valve, and flue dampers close
  • Purge valve opens → purge for 10–15 minutes
  • Only then stop the blower

4. Verify System Status

Cross-check all actions against HMI/SCADA display. Investigate discrepancies immediately.

5. Gas Line Isolation (If Needed)

For extended outages:
  • Request utility team to:
    • Close main gas blind valve
    • يفتح gas vent valve
    • Purge line with نتروجين

6. Controlled Cooling Rate

Prevent refractory damage by managing cooldown speed:
  • Above 800°C: ≤100°C per hour
  • Below 800°C: ≤50°C per hour

اتصل بنا الآن للحصول على تصميم مجاني والاقتباس

قم بالتمرير إلى الأعلى